Gas absorption heat pumps are helping gas distribution operators reduce energy consumption and operating costs at pressure reduction and metering stations.
A recent installation involving an ROBUR GAHP A 35kW gas absorption heat pump demonstrated a 50% reduction in gas self-consumption and a 46% reduction in total operating costs over a 196-day monitoring period.
The results highlight how gas absorption heat pump technology can improve the efficiency of existing gas infrastructure while reducing reliance on traditional boiler systems.
Why Is Gas Preheating Necessary at Pressure Reduction Stations?
Gas pressure reduction and metering stations (PRMS) regulate the pressure of natural gas before it enters local distribution networks.
During pressure reduction, natural gas experiences a significant temperature drop through a process known as the Joule-Thomson effect.
Without adequate preheating, this temperature reduction can cause several operational problems, including:
- Ice and hydrate formation within valves and pipework.
- Increased stress on equipment and components.
- Potential blockages and disruption to gas flow.
- Inaccurate gas metering caused by temperature variations.
- Increased maintenance requirements.
Traditionally, gas-fired boilers have provided the necessary heat to maintain suitable operating temperatures. However, these systems consume a proportion of the natural gas being distributed, resulting in additional fuel costs.
Using high-efficiency commercial and industrial heat pumps for gas preheating offers an alternative approach.
ROBUR Gas Absorption Heat Pump Reduces Gas Consumption by 50%
At one gas pressure reduction and metering station, a single ROBUR GAHP A 35kW gas absorption heat pump was installed alongside the existing gas boiler system.
Rather than replacing the boilers, the heat pump was configured to handle the base load preheating requirements, with the existing boilers remaining available during periods of peak demand.
Over 196 operating days, the installation achieved:
- 50% reduction in gas self-consumption, from 16,668 Sm³ to 8,306 Sm³.
- 46% reduction in total operating costs, including additional electricity consumption.
- Gas Utilisation Efficiency (GUE) of up to 172% for the heat pump technology.
- Electrical input below 1kW, avoiding the need for electrical infrastructure upgrades.
These findings demonstrate the potential for gas absorption heat pumps to reduce the energy required for natural gas preheating while retaining existing heating equipment.
How Do Gas Absorption Heat Pumps Improve Efficiency?
Unlike conventional boilers, which generate heat primarily through combustion, gas absorption heat pumps use a thermodynamic process to recover heat from the surrounding environment.
The ROBUR GAHP A combines natural gas with renewable energy recovered from ambient air to produce useful heating output.
With a Gas Utilisation Efficiency of up to 172%, the system can deliver considerably more useful heat than the energy supplied through the gas it consumes.
The technology also offers several benefits for existing gas infrastructure:
- Low electrical demand: Less than 1kW of electrical input reduces the need for electrical supply upgrades.
- Natural refrigerant: The system uses a water-ammonia absorption cycle, avoiding refrigerants controlled under F-Gas regulations.
- Hybrid operation: Existing boilers can remain in place to provide additional heating during periods of high demand.
- Retrofit suitability: Gas absorption heat pumps can be installed alongside existing heating infrastructure.
- Reduced fuel consumption: Using ambient heat reduces the amount of natural gas required to maintain suitable preheating temperatures.
These features make gas absorption heat pumps particularly relevant for industrial applications where electrical capacity is restricted or where existing gas heating systems remain in operation.
For further information, read our article on gas absorption heat pumps as an alternative heating technology.
Proven Technology Across More Than 140 Gas Distribution Stations
The application of ROBUR gas absorption heat pumps extends beyond this individual installation.
More than 140 gas pressure reduction and metering stations across Italy are now using this technology, including facilities operated by major gas distribution companies.
This established use demonstrates the potential for gas absorption heat pumps to support energy savings across existing gas distribution infrastructure.
For operators considering improvements to their heating systems, incorporating a gas absorption heat pump alongside existing boilers can provide a practical route to reducing operating costs and gas consumption.
Gas Absorption Heat Pump Solutions from Pure Thermal
As a UK partner distributor of ROBUR heat pumps, Pure Thermal supplies a range of commercial gas absorption heat pumps for industrial and commercial heating applications.
Our team provides technical guidance, system design support, equipment supply and commissioning assistance to help businesses assess suitable heating technologies for their requirements.
For organisations looking to reduce gas consumption without extensive electrical infrastructure upgrades, gas absorption heat pumps provide an option worth considering.
Contact Pure Thermal on 020 3488 4618 or email info@purethermal.co.uk to discuss your heating requirements and learn more about the ROBUR gas absorption heat pump range.